GENERAL WELDING SUPPLY CO -- ACETYLENE -- 6830-01-024-4413
===================== Product Identification ===================== Product ID:ACETYLENE MSDS Date:08/22/1989 FSC:6830 NIIN:01-024-4413 === Responsible Party === Company Name:GENERAL WELDING SUPPLY CO Address:1122 WEST ROSECRANS AVE City:GARDENA State:CA ZIP:90247 Country:US Info Phone Num:213-329-7517 Emergency Phone Num:800-640-7517 CAGE:0NBF7 === Contractor Identification === Company Name:GENERAL WELDING SUPPLY CO Address:1122 W ROSECRANS AVE Box:City:GARDENA State:CA ZIP:90247 Country:US Phone:213-329-7517 CAGE:0NBF7 ============= Composition/Information on Ingredients ============= Ingred Name:ACETYLENE CAS:74-86-2 RTECS #:AO9600000 Fraction by Wt: 99% Other REC Limits:2500 PPM (NIOSH) ACGIH TLV:SIMPLE ASPHYXIANT Ingred Name:ARSINE (SARA III) CAS:7784-42-1 RTECS #:CG6475000 Fraction by Wt: 3% PPM OSHA PEL:0.05 PPM ACGIH TLV:0.05 PPM Ingred Name:HYDROGEN SULFIDE (SARA III) CAS:7783-06-4 RTECS #:MX1225000 OSHA PEL:(C),20 PPM ACGIH TLV:10 PPM/15 STEL; 9293 EPA Rpt Qty:100 LBS DOT Rpt Qty:100 LBS Ingred Name:ACETONE (SARA III) CAS:67-64-1 RTECS #:AL3150000 OSHA PEL:1000PPM ACGIH TLV:750PPM/1000STEL;9293 EPA Rpt Qty:5000 LBS DOT Rpt Qty:5000 LBS Ingred Name:PHOSPHINE (SARA III) CAS:7803-51-2 RTECS #:SY7525000 Fraction by Wt: 95% PPM OSHA PEL:0.3 PPM;1 STEL ACGIH TLV:0.3 PPM;1 STEL EPA Rpt Qty:100 LBS DOT Rpt Qty:100 LBS Ingred Name:SUPP DATA:RE-IGNITION COULD OCCUR. IF MATERIAL LEAKING, BUT NOT ON FIRE, DOWN-WIND EVACUATION MUST BE CONSIDERED. RTECS #:9999999ZZ Ingred Name:EXPLO HAZ:ON OTHER CYLS. EXCESS HEAT OR FIRE EXCEEDING 212F WILL CAUSE FUSIBLE SAFETY PLUGS TO RELS ALLOWING (ING 8) RTECS #:9999999ZZ Ingred Name:ING 7:ACETYLENE TO ESCAPE, & IF IGNIT OCCURS, A FLAME AS LONG AS 15 FT COULD DEVELOP. CYLS MAY RUPTURE VIOLENTLY (ING 9) RTECS #:9999999ZZ Ingred Name:ING 8:IF EXPOSED TO EXCESSIVE DIRECT HEAT IMPINGEMENT. ACETYLENE IS LIGHTER THAN AIR & CAN ACCUMULATE IN TOP OF (ING 10) RTECS #:9999999ZZ Ingred Name:ING 9: ENCLOSED SPACES. THERE IS THUS, A POTENTIAL EXPLOSION HAZARD FROM RE-IGNITION. RTECS #:9999999ZZ Ingred Name:CNDTNS TO AVOID:IN ITS CYLINDER. CYLINDERS SHOULD NOT BE EXPOSED TO SUDDEN SHOCK OR SOURCES OF HEAT. RTECS #:9999999ZZ Ingred Name:MATLS TO AVOID:AS IGNIT SOURCES. BRASSES CNTNG LESS THAN 65% COPPER IN THE ALLOY & CERTAIN NICKEL ALLOYS ARE (ING 13) RTECS #:9999999ZZ Ingred Name:ING 12:SUITABLE FOR ACETYLENE SERVICE UNDER NORMAL CNDTNS. ACETYLENE CAN REACT EXPLO WHEN COMBINED W/OXYGEN & (ING 14) RTECS #:9999999ZZ Ingred Name:ING 13:OTHER OXIDIZERS INCLUDING ALL OF THE HALOGENS AND HALOGEN COMPOUNDS. Ingred Name:HAZ DECOMP PRODS:(I.E.:DECOMPOSE INTO CARBON AND HYDROGEN) GIVEN A SOURCE OF IGNITION. RTECS #:9999999ZZ Ingred Name:EFTS OF OVEREXP:LEVELS HAVE NOT SHOWN HARMFUL EFTS. MAJOR TOX PROPERTY IS DISPLACEMENT OF ADEQ SUPPLY OF O*2 TO LUNGS. RTECS #:9999999ZZ Ingred Name:SPILL PROC:SUPPLY LOCATION, OR YOUR LOCAL SUPPLIER. RTECS #:9999999ZZ Ingred Name:OTHER PREC:SOURCES OF IGNIT.ALL ELEC EQUIP SHOULD BE EXPLO PROOF IN STOR/USE AREAS.STOR AREAS MUST MEET NATIONAL(ING 19) RTECS #:9999999ZZ Ingred Name:ING 18:ELEC CODES FOR CLASS 1 HAZ AREAS. EARTH-GROUND & BOND ALL LINES & EQUIP ASSOC W/ACETYLENE SYS. ELEC EQUIP(ING 20) RTECS #:9999999ZZ Ingred Name:ING 19:SHOULD BE NON-SPARKING OR EXPLO PROOF. NEVER USE COPPER PIPING FOR ACETYLENE SERVICE, ONLY STEEL/WROUGHT (ING 21) RTECS #:9999999ZZ Ingred Name:ING 20:IRON PIPE SHOULD BE USED. DO NOT OPEN ACETYLENE CYL VALVES MORE THAN 1/2 TURN. NEVER USE ACETYLENE IN (ING 22) RTECS #:9999999ZZ Ingred Name:ING 21:EXCESS OF 15 PSIG PRESSURE.ACETYLENE CYLS ARE HEAVIER THAN OTHER CYLS BECAUSE THEY ARE PACKED W/A POROUS(ING 23) RTECS #:9999999ZZ Ingred Name:ING 22:FILLER MATL & ACETONE. LEAK CHECK W/SOAPY WATER; NEVER USE A FLAME. REFILLING CYLINDERS W/OUT CONSENT OF (ING 24) RTECS #:9999999ZZ Ingred Name:ING 23:THE CYLINDER OWNER IS A VIOLATION OF FEDERAL LAW (49 CFR). RTECS #:9999999ZZ Ingred Name:VENT:ACETYLENE. MECHANICAL:EXPLOSION PROOF. RTECS #:9999999ZZ ===================== Hazards Identification ===================== LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER. Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO Health Hazards Acute and Chronic:DIZZINESS, HEADACHE, MILD GASTRIC SYMPTOMS, & (IN HIGH CONCENTRATIONS) UNCONSCIOUSNESS, AND DEATH DUE TO THE REDUCTION OF THE OXYGEN LEVEL IN AIR BELOW THAT REQUIRED TO SUSTAIN LIFE. IN GENERAL INDUST RIAL PRACTICES, HOWEVER, ACETYLENE DOESNOT CONSTITUTE A SERIOUS HEALTH HAZARD. IT SHOULD BE NOTED THAT(EFTS OF OVEREXP) Explanation of Carcinogenicity:NOT RELEVANT. Effects of Overexposure:HLTH HAZ:BEFORE SUFFOCATION COULD OCCUR, THE LOWER FLAMM LIMIT OF ACETYLENE IN AIR WOULD BE EXCEEDED; POSS CAUSING BOTH AN O*2-DEFICIENT & AN EXPLO ATMOSPHERE. ACETYLENE IS SIMPLE ASPHYXIANT & ANESTHE TIC. AS NARCOTIC GAS/INTOXICANT, IT CAUSES HYPERCAPNIA (AN EXCESSIVE AMT OF CO IN BLOOD).RPTD EXPOS TO TOLERABLE(ING 16) Medical Cond Aggravated by Exposure:NONE SPECIFIED BY MANUFACTURER. ======================= First Aid Measures ======================= First Aid:ELIMINATE ALL SOURCES OF IGNITION. INHAL:MOVE TO FRESH AIR. IF NOT BREATHING, GIVE ARTIFICIAL RESPIRATION. IF BREATHING DIFFICULT, GIVE O*2. OBTAIN MED ATTN. SKIN:FLUSH W/COPIOUS AMOUNTS OF WATER. CAL L MD . EYE:FLUSH W/POTABLE WATER FOR MINIMUM OF 15 MINS. CALL MD . INGEST:CALL MD IMMED . RESCUE PERS MAY REQ NIOSH/MSHA APPRVD SCBA & SHOULD BE COGNIZANT OF EXTREME FIRE/EXPLO HAZ. ===================== Fire Fighting Measures ===================== Flash Point Method:CC Flash Point:0F,-18C Lower Limits:2.5% Upper Limits:80% Extinguishing Media:CARBON DIOXIDE, DRY CHEMICAL, WATER. Fire Fighting Procedures:WEAR NIOSH/MSHA APPRVD SCBA & FULL PROT EQUIP . SHUT OFF SOURCE OF ACETYLENE IF POSS. EXTING ONLY IF FLOW CAN BE STOPPED. USE WATER IN FLOODING (SUPDAT) Unusual Fire/Explosion Hazard:POSS INCR FIRE INTENSITY & EXPLO HAZ IF CYLS ARE SO PILED OR STACKED THAT BURNING GAS ESCAPING FROM MELTED FUSE PLUG (PRESS RELIEF DEVICE) IS DIRECTED (ING 7) ================== Accidental Release Measures ================== Spill Release Procedures:EVAC IMMED AREA. USE APPROP PROT EQUIP; ELIM ANY POSS SOURCES OF IGNIT, & PROVIDE MAX EXPLO-PROOF VENT. SHUT OFF SOURCE OF ACETYLENE, IF POSS. ISOLATE ANY LEAKING CYL. IF LEAKING FROM CYL, VALVE, OR S AFETY PLUG CNTCT CLOSEST GEN WELDING (ING 17) Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER. ====================== Handling and Storage ====================== Handling and Storage Precautions:STORE & USE W/ADEQ VENT. DO NOT STORE W/IN 20 FEET OF O*2 OR ANY OTHER OXIDIZER. PROTECT CYLINDERS FROM DAMAGE; DO NOT DRAG, ROLL, SLIDE OR DROP. Other Precautions:CYLS SHOULD BE STORED UPRIGHT W/VALVE PROT CAP IN PLACE & FIRMLY SECURED TO PVNT FALLING OR BEING KNOCKED OVER. USE SUITABLE HAND TRUCK FOR CYL MOVEMENT. POST "NO SMOKING OR OPEN FLAMES" SIGNS IN STOR /USE AREAS. THERE SHOULD BE NO (ING 18) ============= Exposure Controls/Personal Protection ============= Respiratory Protection:USE NIOSH/MSHA APPROVED SCBA OR POSITIVE PRESSURE AIR LINE WITH MASK IN OXYGEN-DEFICIENT ATMOSPHERES. RESPIRATORS WILL NOT FUNCTION. Ventilation:PROVIDE SYS ADEQ TO ENSURE ACETYLENE DOES NOT REACH ITS LEL. LOC EXHST:SUFFICIENT TO KEEP AREA BELOW 2.5% (ING 25) Protective Gloves:IMPERVIOUS GLOVES . Eye Protection:CHEMICAL WORKERS GOGGLES . Other Protective Equipment:SAFETY SHOES WHEN HANDLING CYLINDERS. Work Hygienic Practices:NONE SPECIFIED BY MANUFACTURER. Supplemental Safety and Health BOILING PT:-103F, -75C @ 10PSIG. SOL IN H*2O:1.7SCC/100CC H*20@ 32F. VAP PRESS:649.6 PSIA @ 70F. FIRE FIGHT PROC:AMTS AS HEAVY FOG TO COOL ANY BURNING CYLS & SURROUNDING CNTNRS. KEEP UPWIND. EVAC TO R ADIUS OF 1500 FEET FOR UNCONTROLLABLE FIRES. IF FLAME EXTINGUISHED & ACETYLENE CONTINUES TO ESCAPE, AN EXPLO (ING 6) ================== Physical/Chemical Properties ================== Boiling Pt:B.P. Text:SUPP DATA Vapor Pres:SUPP DATA Spec Gravity:0.906 @ 32F Evaporation Rate & Reference:NOT APPLICABLE (GAS) Solubility in Water:SUPP DATA Appearance and Odor:COLORLESS GAS WITH ETHEREAL OR GARLIC-LIKE ODOR FROM IMPURITIES ================= Stability and Reactivity Data ================= Stability Indicator/Materials to Avoid:NO UNDER CERTAIN CNDTNS, ACETYLENE CAN REACT W/COPPER, SILVER, & MERCURY TO FORM ACETYLIDES, CMPDS WHICH CAN ACT (ING 12) Stability Condition to Avoid:DO NOT USE ACETYLENE AT PRESSURES IN EXCESS OF 15 PSIG (30 PSIA). IT IS STABLE BELOW 15 PSI OR IN ACETONE SOLN (ING 11) Hazardous Decomposition Products:ACETYLENE, UNDER PRESSURE CAN, EVEN IF THE ABSENCE OF AIR OR OXYGEN, BE MADE TO EXPLODE VIOLENTLY (ING 15) ==================== Disposal Considerations ==================== Waste Disposal Methods:DO NOT ATTEMPT TO DISPOSE RESIDUAL OR UNUSED CONTAINERS. RETURN TO YOUR SUPPLIER FOR DISPOSAL. DISPOSAL MUST BE IN ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL REGULATIONS . Disclaimer (provided with this information by the compiling agencies): This information is formulated for use by elements of the Department of Defense. The United States of America in no manner whatsoever, expressly or implied, warrants this information to be accurate and disclaims all liability for its use. Any person utilizing this document should seek competent professional advice to verify and assume responsibility for the suitability of this information to their particular situation.